Water System No. : MS0300164 Federal Type : C
Water System Name : JACKSON CO UTILITY AUTHORITY-WEST State Type : C
Principal County Served : JACKSON Primary Source : GW
Status : A Activity Date : 04-25-2012
Lab Sample No. : 100329-001PC Collection Date : 03-26-2010
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1016 CALCIUM 200.8 N MRL 0.480  MG/L
1017 CHLORIDE 300.0 N MRL 28.0  MG/L
1025 FLUORIDE 380-75WE N MRL 0.73  MG/L
1028 IRON 200.8 Y MRL .1 MG/L  
1031 MAGNESIUM 200.8 Y MRL .1 MG/L  
1032 MANGANESE 200.8 N MRL 0.004  MG/L
1042 POTASSIUM 200.8 N MRL 0.319  MG/L
1052 SODIUM 200.8 N MRL 130  MG/L
1055 SULFATE 300.0 N MRL 4.90  MG/L
1057 RESIDUE, TOTAL, FILTERABLE CALCUL LAB N MRL 301  MG/L
1067 ALKALINITY, CACO3 STABILITY 2320B N MRL 22.8  MG/L
1901 CARBON DIOXIDE CALCUL LAB N 0  MG/L
1905 COLOR 2120B N MRL 70  UNITS
1915 HARDNESS, TOTAL (AS CACO3) CALCUL LAB N MRL 1.7  MG/L
1927 ALKALINITY, TOTAL 2320B N MRL 22.8  MG/L
NACA CALCULATED SODIUM CALCUL LAB N MRL 146.3  MG/L
PHFD PH, FIELD RESULT 3500AL-D N MRL 8.9  PH

 

 


Total Number of Records Fetched = 17